Medical Gas Automatic Manifold

*To a quote contact our technical and commercial personnel; Customer information must be valid and true (name, full address, email, telephone, country, zip code, I.D. tax).

**We always request clear specifications to make a formal quote.

Description

Medical Gas full Automatic Manifold to medical applications, complies with NFPA99 and ASTM B819 (clean for oxygen use).

Cabinet:

  • Indoor use, NEMA class 12 IP56 protection level cabinet, in Rittal brand powder coating finish with CE certificate.

Control System:

  • High speed electronic PCB with 7 " full color LCD display, touch screen control.
  • 110-220 vac normally open electric valve.
  • Non-return valves
  • 4-20Map high and low pressure transducers

Graphics:

  • High and Low pressure Display readings primary and secondary cylinder headers in real time.
  • High and Low pressure Display readings of main supply medical gas in real time.
  • Pressure Units.
  • Alarm signals.

Signals (Alarms):

  • Low delivery pressure alarm.
  • Main cylinder header empty alarm.
  • Backup cylinder header in use alarm.
  • High pressure alarm (above of 20% of nominal pressure).
  • Leak alarm (25% pressure drop detected in the reserve or stand by cylinder header).

By-pass System:

  • 2 low pressure final line regulators with manual isolation of stainless steel ball valves (one regulator  in use and the other in reserve).

Over-pressure and vent valve system:

  • Interconnected pipe circuit system protection relief valves, oriented to the exterior of the cabinet manifold.

Emergency Ports:

  • Located after the end line regulators and low pressure only.
  • DISS DEMAND CGA V-5 coupling according to the medical gas of Manifold.

Pressure Gauges:

  • High and low pressure analog type.

Comunication System:

  • 5 Relay type alarms (Dry Contact) to a master panel alarm remote connection, as well an integration of a remote monitoring and administration system BMS (Building Management System) common language based on relay switching.
  • Two-wire Modbus RTU RS485 communication in slave mode for monitoring pressures in PSI units and alarm conditions from a BMS (Building Management System), SCADA (Supervisory Control and Data Acquisition) system or any equipment configured as master panel.
  • Main Cilynder Header use choosing button.
Warning:
 
  • Do not use Oil and its Derivatives.
  • Operation and maintenance personnel must be certified for the manifold safe operation.
  • Quality and Medical Gases Purity Degree, as well condition of containers, cylinders and their connections will be always responsibility of the medical gases supplier.
Manifold Header Hydrostatic Pressure Test

Specifications

Flow Delivery:
  • Standard Flow Delivery of 65 Scf/min.
  • For larger deliveries, consult the factory in advance.
Cylinder Headers:
  • Modular Assembly.
  • Red brass tube special extrusion SPS alloy 23000, H58 Drawn temper made, complies with ASTM B-43-98, ASTM B-819 (Clean for oxygen use) 3,000 PSI working pressure.
  • CGA connection points for each cylinder with self-closing non-return valves (check) brass made.
  • Manual master valve to opening and closing control of the primary and secondary cylinder headers.
Connection Cylinder Gas Pigtails:
  • Oxygen: Flexible Copper pipe CGA 540 connection.
  • Other Non-Corrosive Gases: Flexible PTEF hose with stainless steel mesh covering and lifeline, in CGA connection for the specific gas.
Available for:
  • High Pressure Gas Cylinders Only
Available for the following Gases:
  • Medical Oxygen
  • Medical Air
  • Nitrous oxide
  • Nitrogen
  • Carbon dioxide
  • Helium
  • Argon
Requires:
  • 100-220 V 50-60 Htz. power supply.
Wire type network system connection:
  • Belden STP (Shield Twisted Pair) #8461ZH or #8208.
Effects on the Equipment operation that must be avoided:
  • Voltage variations in the electrical power supply.
  • Main power supply with emergency power plants.
  • Intermittent Power supply (power lost and regained often in a short time).
Installation recommendations:
  • Check ground connection (to protect from unwanted discharges).
  • Install a system against voltage variations and power backup (Non-Break).
  • Install a system with a surge suppressor (against power surges and discharges).

Brochure

Download:
Medical Gas Automatic Manifold.
Intellectual and industrial property: All rights reserved.
  • All access to this website is subject to the following conditions: The reproduction, permanent storage and dissemination of the contents or any other use that has a public or commercial purpose is forbidden without prior written notice and approval of Grupo Arigmed S. de R.L. de C.V.
  • All documents, images and contents, on this website are from the Intellectual property of Grupo Arigmed S. de R.L. de C.V., any type of copy, plagiarism or similarity in those (documents, images and contents), will be object of legal actions to avoid its use by unauthorized persons, organizations or companies, as well to compensate author´s damage caused.

 